AXISA1001NetworkDoorController&AXISEntryManager
AlarmandEventConfiguration
-AreaChangedNotsupportedbythisversionofAXISEntryManager.Mustbeconguredbyaclientsuchasan
accessmanagementsystem,throughtheVAPIX®applicationprogramminginterface,thatsupportsthisfeature
andusedevicesthatcanprovidetherequiredsignals.Triggerstheactionrulewhenanaccessareaischanged.
-AreaRemovedNotsupportedbythisversionofAXISEntryManager.Mustbeconguredbyaclientsuch
asanaccessmanagementsystem,throughtheVAPIX®applicationprogramminginterface,thatsupportsthis
featureandusedevicesthatcanprovidetherequiredsignals.Triggerstheactionrulewhenanaccessareais
removedfromthesystem.
-DoorChangedTriggerstheactionrulewhenthedoorcongurationsettings,forexampledoorname,are
changedorwhenadoorisaddedtothesystem.Thiscanforexamplebeusedtosendanoticationwhena
doorisinstalledandcongured.
-DoorRemovedTriggerstheactionrulewhenadoorisremovedfromthesystem.Thiscanforexamplebe
usedtosendanoticationwhenadoorisremovedfromthesystem.
Door
-BatteryAlarmTriggerstheactionrulewhenawirelessdoorbatteryislowandwhenitisat.
-DoorAlarmTriggerstheactionrulewhenthedoormonitorindicatesthatthedoorhasbeenforcedopen,the
doorisopentoolong,orifthedoorisfaultyinanyway.Thiscanforexamplebeusedtosendanotication
whensomeoneisforcinganentry.
-DoorDouble-LockMonitorTriggerstheactionruleonlywhenthesecondarylockchangesstatetoeither
lockedorunlocked.
-DoorLockMonitorTriggerstheactionrulewhenthenormallockchangesstatetoeitherlockedorunlocked.
Forexample,afaultistriggeredwhenthedoormonitordetectsthatthedoorisopenalthoughthelockislocked.
-DoorModeTriggerstheactionrulewhenthedoorchangesstates,forexample,whenthedoorhasbeen
accessedorblocked,orthedoorisinlockdownmode.Formoredetaileddescriptionsofthesemodes,seethe
onlinehelp.
-DoorMonitorTriggerstheactionrulewhenthedoormonitorstatechanges.Thiscanforexamplebeusedto
sendanoticationwhenadoormonitorindicatesthatthedoorisopenedorclosed.
-DoorTamperTriggerstheactionrulewhenthedoormonitordetectsthattheconnectionisinterrupted,for
exampleifsomeonecutsthewirestothedoormonitor.Tousethistrigger,makesurethatEnablesupervised
inputsisselectedandthatendoflineresistorsareinstalledontherelevantdoorconnectorinputports.For
moreinformation,seeUseSupervisedInputsonpage19.
-DoorWarningTriggerstheactionrulebeforethedooropentoolongalarmgoesoff.Thiscanbeusedto,
forexample,sendawarningsignalthatthedoorcontrollerwillsendtherealalarm,thedooropentoolong
alarm,ifthedoorisnotclosedwithinthespecieddooropentoolongtime.Formoreinformationaboutdoor
opentoolongtime,seeCongureLocksandDoorMonitorsonpage16.
-LockJammedTriggerstheactionrulewhenawirelessdoorlockisphysicallyblocked.
EventLoggerKeepstrackofalleventsinthedoorcontroller,forexamplewhenauserswipesacardoropensadoor.If
Globaleventsisenabled,theeventloggerkeepstrackofalltheeventsineverycontrollerinthesystem.Tosetwhich
alarmsandeventsthatcantriggeranactionrule,gotoSetup>CongureEventandAlarmLogs.Theeventloggeris
sharedbythesystemandcanstoreupto30000events.Whenthelimitisreached,theeventloggerusestherstinrst
out(FIFO)rule.Thismeansthatthersteventisthersttobeoverwritten.
-AlarmTriggerstheactionrulewhenoneofthespeciedalarmshasbeentriggered.Thesystemadministrator
cancongurewhicheventsaremoreimportantthanothersandselectwhetheraparticulareventshould
triggeranalarmornot.
-DroppedAlarmsTriggerstheactionrulewhennewalarmrecordscannotbewrittentothealarmlogs.For
exampleiftherearesomanysimultaneousalarmsthattheeventloggercannotkeepup.Whenanalarmis
dropped,anoticationcanbesenttotheoperator.